PLPro-40/80A-iV

leutron
Technical Data PLPro-40 PLPro-80
Rated voltage (P-E) Umax 25 V= 25 V=
Max. continuous diverting current 50Hz (P-E) IA 40 A~ 80 A~
Short-time discharge current for 1s/50Hz (P-E) Imax 400 A~ 800 A~
Leakage current (P-E) ≤ 1 mA ≤ 1 mA
Nominal discharge current (8/20 µs) (P-E) In 10x 100 kA 10x 100 kA
Lightning impulse current (10/350 µs) Iimp 100 kA 100 kA
Capacitance condensators C 2x 100.000 µF
Operating temperature range TU -40 – +80 °C -40 – +80 °C
Terminals (P/E) min. 16 / max. 150 mm² min. 16 / max. 150 mm²
Current transformer 100:1 A 100:1 A
Terminals (current transformer i1, i2) 25 mm² 25 mm²
Mounting wall mounting wall mounting
Degree of protection (IEC EN 60529) IP 65 IP 65

PRI-3000

indicator
PRI-3000
ALARM INPUT OUTPUT POWER
None Multi None 95~250V
2-Alarm Other 4~20㎃ DC24V
4-Alarm   Other  
    Com.  

Model PRI-3000 Power AC110/220V (60㎐) ±10% / 4.0VA
Power Consumption DC24V ±25% / 100㎃ Display -9999~9999, 7 Segment & 4 Digit
Accuracy ±0.2% Full Scale

 

±1 Digit (25℃ ± 5℃)

Input Impedance V Type 1㏁

 

RTD, T/C Type 1㏁

Sampling Cycle V Type 200㎳

 

RTD, T/C Type 400㎳

2-Wire Sensor Voltage DC24V / 30㎃ (±5% or less)
Temperature Coefficient ±0.015% / ℃ Insulation Resistance Greater than 100㏁ with DC500V
Operating temperature/humidity -10~60℃ / 90% Storage temperature/humidity -20~80℃ / 95%
Weight 400g Mounting Panel Mounting Type

SHN-PMC

SHN-ISO-5
SHN-IPS
INPUT OUTPUT 1 OUTPUT 2 POWER
2-Wire(12V) 0~10V 0~10V AC110V
2-Wire(24V) 1~5V 1~5V AC220V
Other 4~20㎃ 4~20㎃ DC24V
Other Other
None

—————

Model SHN-Series Function Transmit DC signal in isolated conditon
Input mA, RTD, 2-Wire, Potentiometer, T/C, Pulse, CT, PT Output DC Siganl (4-20mA, 1-5V) Max : 2ch
Power DC 24V, AC 110V or AC 220V Accuracy 0.1% / Full scale
Display None Response Time 0.5 sec (0~90%)
Front Adjustment Zero and Span 5% Weight About 400g
Mounting DIN Rail mounting Dimensions(mm) W50 * H85 * D 122/133 (8PIN / 11PIN)