Presentation
4개의 격리된 디지털 입력(Dry contacts) 또는 임펄스(NPN, PNP)로 UHLIS 0040T0을 통해 4개 모두를 유연하게 구성할 수 있습니다
모드버스 RTU 연결을 통한 상태 전송 또는 임펄스 카운팅을 위한 입력. UHLIS 0040T0는 5년이 보장됩니다
Inputs |
Functioning mode |
Counting direction |
Scale factor value |
Counter reset value |
Counting |
Increasing |
1.0 |
0.0 |
|
Alarms thresold mode |
Alarm 1 thresold |
Alarm 1 thresold |
|
|
Unused |
0.0 |
0.0 |
|
|
Functions |
Function performed |
Operand A |
Operand B |
Operand C |
Unused |
Input 1 |
Input 1 |
Input 1 |
- Inputs – Communication
- Input gauges
Input |
4 digital inputs: NPN, PNP, dry contacts Acceptable voltage range 0-24V Vil: 2V ; Vih: 10V |
Sensor supply |
2 wires sensor 24V ; 41mA max |
Communication |
Isolated USB front panel / Isolated RS485 Modbus RTU |
- Characteristics
Input characteristics |
|
Current input impedance |
> 4.7 kΩ Active state >11 MΩ Passive state |
Isolation |
|
Supply / Inputs-Communication |
4200Vrms, 50Hz,1mn |
Input x / Input y / USB-RS485 |
2500Vrms, 50Hz,1mn |
USB / RS485 |
Without |
Auxiliary source |
|
Voltage supply |
22-240Vdc or 90-230Vac 50/60Hz |
General characteristics |
|
Max frequency of counting / of a digital signal |
Counting max frequency: 1 channel: 2.4 kHz ; 2 channels: 2.2 kHz ; 3 channels: 2 kHz ; 4 channels: 1.8 kHz |
Maximum of consumption |
<5 VA |
Operating temperature |
-10°C … +60°C |
Storage temperature |
-25°C … +80°C |
Relative humidity |
<95% HR (non-condensing) |
Protection factor |
IP20 |
- Functions
Display functions |
|
LED indicators |
4 red LEDs light up or down depending on the state of the input 1 LED indicates that a communication is in progress (USB or RS485) |
Programming |
Programming via USB with IXLOG software |
Smart functions |
|
Calculation mode |
Functions configurable: A+B, A+B+C, A+B+C+D, A-B, A/B, (A-B)/A |
Memorization of Digital input states |
Copy status of digital inputs to bits for transmission via Modbus |
Counter input |
Counting direction: increase, decrease Possibility to enter a multiplier factor on the value of each input Possibility to define 2 alarm thresholds per channel Possibility to reload the counter with an initialization value set when the second threshold is exceeded Reloading a counter with an initialization value by setting a bit |
Links and communication |
|
RS485 MODBUS RTU |
RS485 MODBUS RTU bidirectional digital link allowing to: recover the measurements and transmit them in digital format configure and control the device |
USB front |
USB front panel to connect directly to the USB port of a PC for programming via the IXLOG software |